Мультифункциональный индикатор может измерять токовый или потенциальный сигнал. Может использоваться с двухпроводными токовыми трансформаторами, датчиками давления, тензометрами, резистивными трансмиттерами давления, потенциометрами и другими сенсорами.
Main features
Port signal description


Special note: In the third-level menu, click OK to save the modified parameter value and return to the previous menu, the parameter number is automatically increased by one; and click the SET button to directly return to the previous menu without saving the modified parameter value .Long press
or
to make the adjustment value change quickly.

The parameters are described as follows:
1. F0 Attendant array display
|
Parameter |
parameter name |
Scope and description |
Defaults |
read / write |
|
F0-0 |
Collected value monitoring |
Monitor the percentage of the current analog input value. Range: 0-100.0% |
|
read-only |
|
F0-1 |
Display value monitoring |
In the display value in "Monitoring Menu" is calculated by F0-0, F0-2~F04. |
|
read-only |
|
F0-2 |
Display accuracy |
The number of decimal places displayed in the "Monitor Menu", range: 0-3. |
1 |
read / write |
|
F0-3 |
Show minimum |
In the "monitoring menu", the value corresponding to "acquisition value" is 0%, the range: -1999~9999 |
0 |
read / write |
|
F0-4 |
Show maximum |
In the "Monitoring Menu", the value corresponding to the "Acquisition Value" is 100.0%, the range: 1999~9999 |
1000 |
read / write |
|
F0-5 |
Offline status |
|
|
read-only |
2. F1 parameter group-analog configuration parameters
|
Parameter |
parameter name |
Scope and description |
Defaults |
|
F1-0 |
Input type selection |
|
0 |
|
F1-1 |
Input filter time |
Analog input filter time, range: 0~10.000s. The longer the filtering time, the stronger the filtering |
0.200 |
|
F1-2 |
Input gain |
Range: 0~1000.0%. |
100.0 |
|
F1-3 |
Input offset |
-99.9~99.9%, with 10V or 20mA as 100.0%. |
0.0 |
|
F1-4 |
Drop detection threshold |
Range: 0.0-100.0%. This value is based on 0-10V or 0-20mA as 0.0-100.0% as a reference (and F1-0 and gain offset are not related), the detection is not started if it is less than 0.5, and there is a hysteresis of ±0.3. When the input signal is lower than this value, the meter displays E.oFL. (Starting from V2.10) |
0.0 |
|
F1-5 |
Enter the parameter setting selection |
|
0 |
The analog input gain and offset use formula is: adjustment result = (collected value + offset) × gain, the adjustment result is limited to 0.0~100.0%
The range is 100.0% when greater than 100.0%, and 0.0% when less than 0.0%